Characteristics of the control unit FAS
- Up to 7 detection loops
- Up to 250 elements per a loop
- Up to 250 supervisory zones per a loop
- Outputs built-in
- ATE
- Signal lines
- Fault
- Universal relay
- Maximum loop length 2 km
- Loop interval detection
- Events counter up to 15,000
- Expansion cards
- Conformity with EN 54-2, EN 54-4 standard
- 7-Inch touch screen
- Printer built-in
- BACnet interface
Optionally, the control units may be configured through the TCP/IP protocol. Access to the system is available through dedicated software or on the website.
Application of the RJ-45 connector and the IP technology allows to integrate the system and the building management systems (BMS), with the Safety management systems (SMS) and the visualisation systems (SMART VISIO).
TYPE:
addressable
POWER SUPPLY:
170-260 V AC 50 Hz
OUTPUT POWER:
20-30 V DC
BATTERIES:
26 Ah / 52 Ah
WIRES CROSS-SECTIONS:
2,5 mm2 maximum
DETECTION LOOPS WIRE COSS-SECTION:
0,8-1,5 mm2
LENGHT OF DETECTION LOOP:
2 km
TYPE OF DETECTION CIRCUIT:
detection loop, stub detection circuit, side stub detection circuit
MAXIMUM NUMBER OF DETECTION LOOPS:
7
MAXIMUM NUMBER OF STUB DETECTION CIRCUIT:
14
MAXIMUM NUMBER OF DETECTION ZONES:
250 per loop
MAXIMUM NUMBER OF ELEMENTS ON DETECTION LOOP:
250
MAXIMUM NUMBER OF ELEMENTS ON STUB DETECTION CIRCUIT:
32
NUMBER OF SIGNAL LINES:
2
ALARMING VARIANTS:
16
UNIVERSAL INPUTS:
8 maximum
UNIVERSAL RELAY OUTPUTS:
9 maximum
EVENTS COUNTER:
15000
PERMISSIONS LEVELS:
4 levels
PRINTER
yes, optionally
LAN INPUT
yes
CASING:
powder-coated steel, RAL 3000
PROTECTION LEVEL:
IP 30
WORKING TEMPERATURE:
from 10º C to 40º C
DETECTION LOOPS CARD KPD 2
INSTALLATION:
inside the FAS control unit
NUMBER OF DETECTION LOOPS:
2
TYPE OF DETECTION CIRCUITS:
detection loop, stub detection circuit, side stub detection circuit
MAXIMUM NUMBER OF ELEMENTS ON DETECTION LOOP:
250 per loop
MAXIMUM LENGHT OF DETECTION LOOP:
2 km
MAXIMUM NUMBER OF CARDS:
3
PRODUCT CODE:
FSC0000001
INPUT/OUTPUT CARD KIO 22
INSTALLATION:
inside the FAS control unit
MONITORING:
input signal monitoring
NUMBER OF INPUTS:
2 supervised inputs
NUMBER OF OUTPUTS:
2 relay outputs
MAXIMUM INPUT LOAD:
30 V DC 0,5 A
MAXIMUM NUMBER OF CARDS:
3
PRODUCT CODE:
FSC0000002
COMMUNICATION CARD KRS 422
INSTALLATION:
inside the FAS control unit
MAXIMUM NUBER OF EXTERNAL SIGNAL PANEL
10
MAXIMUM LENGHT OF A WIRE:
1 km
MAXIMUM NUMBER OF CARDS:
1
CONNECTION TYPE:
doubled loop
PRODUCT CODE:
FSC0000003
FAS control units can be combined to create the network of correlative control units. On the communication line of the network it is also possible to connect the ESP remote panels which allow to control the condition of each of the control units, as well as configure particular control units.