Specifications | Units | DT 16 |
---|---|---|
Nominal recirculation air flow |
m³/h
|
12,000
|
Exhaust/fresh air flow (stepped control) |
m³/h
|
850-8,000
|
Total dehumidification @ 28°C/60% RH by heat pump and maximum fresh air |
l/h
|
62.4
|
Heat to air | ||
Via heat pump (Mode B) |
kW
|
35.0
|
Via standard LPHW @ 80°C |
kW
|
90
|
Via upgraded LPHW @ 55°C |
kW
|
77
|
Total Mode B + standard LPHW |
kW
|
125.0
|
Heat to pool water | ||
Via heat pump (Mode A) |
kW
|
43.0
|
Via LPHW @ 80°C |
kW
|
65
|
Via LPHW @ 55°C |
kW
|
32
|
Total Mode A + LPHW |
kW
|
108.0
|
Cooling duty | ||
Total |
kW
|
-28.0
|
Sensible |
kW
|
-15.0
|
Nominal power consumed |
kW
|
17.0
|
R407c gas weight/CO2 equivalent |
kg/t
|
21.5/38.14
|
Width |
mm
|
2,860
|
Depth |
mm
|
1,126
|
Height |
mm
|
2,120
|
Weight |
kg
|
1,020
|