- 1-pair DIN rail plug-in Data surge protector
- Standards compliance: IEC 61643-21 / EN 61643-21
- Technology: GDT + Clamping diode
- SPD configuration: 1 pair
- Network: 4 … 20 mA
- Max. DC operating voltage: 32 VDC
- Max. discharge current : 20 kA
DLA protects information and communication technology, telecommunication equipment and data technology systems from lightning effects and surges.
The electrical circuit of the DLA consists of a combination of high-performance gas discharge tubes and fast-switching diodes for high discharge capacity and fast response behaviour.
The shield connection is additionally earthed via a gas discharge tube. The earthing connection is conveniently made via the top-hat rail. When the plug-in module is unplugged, the transmission signal is not interrupted.
| Characteristic | Description / Value | |
|---|---|---|
| Nominal line voltage | Un | 24 V |
| Max. DC operating voltage | Uc | 32 V DC |
| Max. discharge current max. withstand @ 8/20 μs by pole |
Imax | 20 kA |
| Protection level Following the test category C3 (IEC61643-21) – Line/Line |
Up | 60 V |
| Protection level Following the test category C3 (IEC61643-21) – Line/PE |
Up | 650 V |
| Nominal discharge current C2 Category |
In | 10 kA |
| Operating and storage temperature | -40 … +85 °C | |
| Protection rating | IP 20 | |
| Manufacturer | Citel | |