Specifications |
Units |
RCV 320 |
Maximum flow at 100Pa |
V | m³/h |
320 |
Maximum rated flow at 100Pa |
Vmax | m³/h |
200 |
Operating range DIBt |
VDIBt | m³/h |
70 - 200 |
Operating range Passivhaus at 100Pa |
VPHI | m³/h |
70 - 160 |
EN 13141-7 reference flow at 50Pa |
VREF | m³/h |
140 |
Performance |
% |
<2% (Class A1) |
Thermal efficiency in accordance with PHI |
ηSUP | % |
92 |
Thermal efficiency in accordance with EN13141-7 |
ηSUP | % |
90 |
Leakage (external and internal) in accordance with EN 13141-7 |
- |
<2% (Class A1) |
Filters in accordance with ISO16890 |
- |
ISO Coarse 75% (optional on supply: ePM1>50%) |
Filters in accordance with EN779 |
- |
G4 (optional on supply: F7) |
Installation surrounding temperature |
tSURR | °C |
-12 to +50 |
Outdoor temperature without preheater installed |
tODA | °C |
-12* to +50 |
Outdoor temperature with preheater installed |
tODA | °C |
-20 to +50 |
Maximum absolute humidity of extract air |
x | g/kg |
10 |
Cabinet |
- |
70 |
Dimensions (without bracket) |
mm | w x d x h |
600 x 603 x 526** |
Spigots/ducts connections |
Ømm |
8 pcs ø125 and 2 pcs oval (68 x 163) – female |
Weight |
kg |
35 |
Thermal conductivity – polystyrene insulation |
λ | W/mK |
0.031 |
Heat transition figures – polystyrene insulation |
U | W/m²K |
U<1 |
Fire classification of the polystyrene insulation |
class |
DIN 4102-1 class B2 |
Drainage hose included |
Ø/length | "/m |
ø¾" – 1m |
Cabinet colour |
RAL |
no paint/raw Alu-zinc |
Electrical |
- |
|
Voltage |
U | V |
230 |
Maximum power consumption (without/with preheater) |
P | W |
170/1070 |
Frequency |
f | Hz |
50 |
Protection class |
- |
IP21 |