Technical Data
Article name PA2210CE08 Air curtain
Article number #19422
Default
|
|||
---|---|---|---|
Installation | |||
Type of installation | Horizontal | ||
Recommended installation height | 2.2 | m | |
Nominal data | |||
Color casing | Traffic white | ||
Color casing, RAL | RAL 9016 | ||
Color, outlet grilles | Telegrey 2 | ||
Color outlet grilles, RAL | RAL 7046 | ||
Enclosure class | IP20 | ||
Ambient working temperature (dry conditions) | -20 to 30 | °C | |
Dimensions and weights | |||
Length | 1,050 | mm | |
Height | 210 | mm | |
Depth | 345 | mm | |
Weight | 19 | kg | |
Air flow | |||
Air flow | 900; 1200; 1000 | m³/h | |
Sound data | |||
Sound pressure (LpA) | 51; 47; 42 | dB(A) | |
Conditions sound pressure | Conditions: Distance to the unit 5 metres. Directional factor: 2. Equivalent absorption area: 200 m². | ||
Sound power (LWA) | 67 | dB(A) | |
Conditions sound level | Measurements according to ISO 27327-2: 2014, Installation type E. | ||
Motor/control supply | |||
Control/motor supply | 230 | V | |
Control/motor current | 0.45 | A | |
Input power (P1), motor | 110 | W | |
Electric heat | |||
Heat output | 8; 5 | kW | |
Heat amperage | 11.5; 7.2 | A | |
Heat voltage | 400 | V | |
Phases | 3N~ | ||
Temperature rise, maximum heat output, highest airflow | 20 | °C | |
Temperature rise, maximum heat output, lowest airflow | 27 | °C |